C:
DATA
< INC > < ENT >
INC
ENT
:
"FLOW" is displayed
when output mode is
square root extraction
mode.
:
"
flicker" is displayed
when the communica-
tion between transmitter
and HHC is normal.
ENT
D:
SELF CHECK
< INC > < ENT >
1
INC
Temperature is displayed in C and F
alternately at each press of the <INC> key.
E:
PRINT
[Contents of message]
As a result of self-diagnosis, the message below is appeared on the LCD display of HHC, when there are
trouble in the transmitter. For each error, its cause and remedy are suggested.
Message
Indication on digital indicator
CELL FAULT (C1)
(*1)
CELL FAULT (C9)
EEPROM (AMP) FLT
EEPROM (CELL)
FLT
TEMP. ALARM
XMTR FAULT
(*1) Real indication
TN5FCXA2V5h-E
B
DATA
C-1:
DATA
XXX. X %FLOW
XXXXX kPa
< CHANGE > < CL >
CHNG
CL
C-1: DATA
XXX. XX %FLOW
XXXXX
kPa
< CHANGE > < CL >
CHNG
CL
(HHC is not used for 10 minutes)
STANDBY
PUSH CL KEY
CL
D-1: SELF CHECK
< 1 > AMP TEMP
< 2 > ALM CHECK
< 1 > < 2 > <CL >
2
1
2
CL
D-2: SELF CHECK
TEMP=XXX.X C
(YYY.Y F)
< CL > <INC>
3
CL
D-2:
SELF CHECK
ALM CHECK
GOOD
< CL >
CL
4
(Temperature alarm is displayed)
D-2:
SELF CHECK
TEMP=XXX.X C
TEMP.ALARM
INC
5
(Trouble in transmitter)
D-2:
SELF CHECK
CELL FAULT (C1)
< CL > < INC >
CL
6
Error of detecting unit
FL-1
FL-2
EEPROM error on cell side
FL-3
(*1)
Transmitter temperature is not within the allowable
T.ALM
ZERO
range (–40 to 85°C).
FL-1
(*1)
OVER
Input pressure is 105% or higher of setting range.
ZERO
Under
(*1)
Input pressure is –1.25% or lower of setting range.
ZERO
Menu C : Indication of measuring data
The measured value is indicated.
Flashing "*" indicates the transmisstion of the mea-
surement valu to the HCC.
the digital number for the "%" can be set pressing
"CHNG".
The HCC will be in stand by after 10 min without any
operation. Press "CL" to avoid the stand by and come
back to the display with the measuring data...
Menu D : Self-diagnosis
Use for displaying the measured temperature in
the transmitter and the alarm information.
about transmitter (ALM CHECK) is displayed.
Result of diagnosis
D-2:
SELF CHECK
When temperature alarm is detected:
D-2:
SELF CHECK
TEMP. ALARM
When no error has occurred:
D-2:
SELF CHECK
ALM CHECK
GOOD
When an error has occurred:
D-2:
SELF CHECK
CELL FAULT (C1)
For contents of error, refer to "Contents of mes-
sage".
Cause
, the tempera-
Remedy
Replacement of detecting unit
Replacement of detecting unit
Transmitter temperature is normalized.
Properly controlled.
Properly controlled.
81