4.1 Wiring procedure :

Sealing of conduit connection
To insure air tightness of the connection box, use sealing tape
with metal pipe screw coupling or rubber gasket fastening
gland
INDICATION
Terminal block connection diagram
Tighten the terminal screws (M4x10) to a torque of ap-
will not loosen.
After connection, fasten the cover until it does not turn.
Wiring diagram
Transmitter
When using an external indicator
nect the "+" and "–
CK– of the transmitter as shown below.
INDICATION
TN5FCXA2V5h-E
1. If the conduit connection is located on the top side of the transmitter
when using a protective tube for the wiring, then water may enter into
the protective tube and have an adverse effect on the transmitter.
2. The thread of tube connection should match with the transmitter con-
duit thread.
DC power supply
Load resistance
Take care to respect the polarity when connecting the terminals
Metal pipe
Terminal
Output DC
4 to 20mA
4 to
Terminal
20mA DC
-
Output DC
4 to 20mA
Converter
10.5 to
45 V DC
Converter
10.5 to
45 V DC
33