G-8 : LOW CUT
POINT=XX.XX%FLOW
MODE=YYYYYY
<CHANGE><CL>
CL
CHNG
or
1
24
G-9 : POINT CHANGE
XX.XX%FLOW
<ENT><CL>
ENT
CL
22
25
G-9 : POINT CHANGE
XX.XX%FLOW
CHNG OK?<ENT/CL>
CL
ENT
26
G-A : POINT WRITE
XX.XX%FLOW
27
G-B : LOW CUT MODE
LINEAR
<CHANGE><CL>
CL
CHNG
or
1
28
G-C : MODE CHANGE
<1>LINEAR
<2>ZERO
<1><2><CL>
CL
1
2
29
G-D : MODE CHANGE
LINEAR
CHNG OK?<ENT/CL>
ENT
CL
28
30
G-D : MODE WRITE
LINEAR
TN5FCXA2V5h-E
2
Note2) CUT POINT
and
CUT MODE
are set at Menu No.8
YYYYYY=LINEAR or ZERO
24
27
G-B : LOW CUT MODE
ZERO
<CHANGE><CL>
CL
CHNG
2
1
27
29
G-B : MODE CHANGE
ZERO
CHNG OK?<ENT/CL>
ENT
CL
28
30
G-B : MODE WRITE
ZERO
Low cut point setting for square root mode
After choosing <2
display
• Press <CHANGE
Cut point is adjustable within the range of 0.00 to
20.00 %.
Note :
If the cut point is set to small value around 0%
even a minute differential pressur change causes
The cut point is used for improving the measure-
• Press <ENT
to cancel.
Low cut mode setting for square root mode
After setting the low cut point, it is possible to set
the low cut mode : Linear or Zero.
There are two modes :
Output
or
2
Low cut
point
Fig. A: With linear output
selected in low cut mode
• Press <1
• Press <ENT
to cancel.
(Flow mode choosen)
Output
Low cut
point
Differential
input
Fig. B: With zero output
selected in low cut mode
2
(actual display
2
CL
Differential
input
CL
85