INSTALLATION AND PIPING

Type
Ambient
temperature
limit
Differential
-40 to 85°C
pressure
Gauge
-40 to 85°C
Pressure
Absolute
-40 to 85°C
Pressure
Level and
-40 to 85°C
remote seal(s)
*
Refer to "technical datasheets" about details of process temperature limits of the transmitters.
INDICATION
TN5FCXA2V5h-E
Process
temperature
limit
-40 to 120°C
(silicone oil)
-20 to 80°C
-40 to 100°C
(silicone oil)
-20 to 80°C
-40 to 85°C
See note*
Protect the transmitter with a security device when the existing application
conditions require it. The transmitter should be installed remote from the
measuring point in the case that the process temperature is too high.
Span
Static pressure
limit
limit
10 mbar
-1 to 32 bar
60 mbar
-1 to 100 bar
320 mbar
-1 to 160 bar
(option : 420 bar)
(option : 420 bar)
5 bar
-1 to 160 bar
(option : 420 bar)
30 bar
-1 to 160 bar
(option : 300 bar)
200 bar
-1 to 300 bar
1,3 bar
-1 to 1,3 bar
5 bar
-1 to 5 bar
30 bar
-1 to 30 bar
100 bar
-1 to 100 bar
0,16 bar abs
0 to 0,16 bar abs
1,3 bar abs
0 to 1,3 bar abs
5 bar abs
0 to 5 bar abs
30 bar abs
0 to 30 bar abs
100 bar abs
0 to 100 bar abs
60 mbar
According PN/lbs
320 mbar
of remote seal
1300 mbar
5000 mbar
30000 mbar
100 bar
200 bar
500 bar
Technical
datasheets
EDSF6-134
EDSF5-92
and
EDSF5-98
EDSF5-91
and
EDSF5-97
EDSF7-68
EDSF6-05
and
EDSF6-06
11