6-2 : Change of URV (upper limit of the measuring
• Press the
screen for setting the 100% point ( ).
• Input the numerical values with the
SPAN
the screen
Functions of the keys:
key: To decrease the value.
key: To increase the value.
Note)
If "UUUUU" is displayed as a URV value, the
SPAN
unit is not supported.
• To set the decimal point position, press the
the screen
name ( ) and you can set the decimal point position
with the
and
key: To move the decimal point position to left
SPAN
key: To move the decimal point position to right
• Select whether the URV setting is saved on the
screen
.
Press the
Press the
Important
The setting range of the transmitter is independant
ot the setting range of the indicator.
After changing the range in this menu, it is neces-
sary to change the range in the LCD indicator
(menu G).
Using an analog indicator and if the transmitter
range is changed, replacement of the analog indi-
cator is required.
key on the screen
.
. "P" is displayed at the left of the unit
keys.
key to save the 100% point setting.
or
key to cancel the setting.
to display the
and
keys on
key on
49