5.2 Operation

(1) Gauge (FKG) and absolute (FKA) pressure transmitter :
Open the valve slowly to apply a pressure.
When pressure is applied, the transmitter is set in the
operating status.
Set the operating status by manipulating
the isolating valve.
Make sure the equalizing valve is open and
make the zero adjustement (0%)
Open the isolating valve on the HP side slowly.
Close the equalizing valve.
Open the isolating valve on the LP side slowly
TN5FCXA2V5h-E
Close the isolating
valve the LP side
Open
Equalizing
valve
Close
Open
Open
close isolating
valve on the
HP side
Open
37