Parameters
8-53 Start Select
Option:
3
3
[0] Digital
input
[1] Bus
[2] Logic AND Activates Start command via the serial communi-
[3] Logic OR
8-54 Reversing Select
Option:
[0] Digital
input
[1] Bus
[2] Logic
AND
[3] Logic OR
8-55 Set-up Select
Option:
3-38
VLT
Function:
Select control of the adjustable frequency drive
start function via the terminals (digital input).
NOTE!
This parameter is active only when
8-01 Control Site is set to [0] Digital and
control word.
Activates Start command via a digital input.
Activates Start command via the serial communi-
cation port.
cation port, AND additionally via one of the
digital inputs.
Activates Start command via the serial communi-
cation port OR via one of the digital inputs.
Function:
Select control of the adjustable frequency drive
reverse function via the terminals (digital input)
and/or via the serial communication port.
NOTE!
This parameter is active only when
8-01 Control Site is set to [0] Digital and
control word.
Activates Reverse command via a digital input.
Activates Reverse command via the serial
communication port.
Activates Reverse command via the serial
communication port, AND additionally via one of
the digital inputs.
Activates Reverse command via the serial
communication port OR via one of the digital
inputs.
Function:
Select control of the adjustable frequency drive
set-up selection via the terminals (digital input)
and/or via the serial communication port.
MG18B222 - VLT
®
HVAC Basic Drive Programming Guide
8-55 Set-up Select
Option:
[0] Digital
input
[1] Bus
[2] Logic
AND
[3] Logic OR
8-56 Preset Reference Select
Option:
[0] Digital
input
[1] Bus
[2] Logic AND
[3] Logic OR

3.8.4 8-7* BACnet

8-70 BACnet Device Instance
Range:
1
[0 - 4194303 ] Enter a unique ID number for the BACnet
*
8-72 MS/TP Max Masters
Range:
127
[0 - 127 ] Define the address of the master which holds
*
®
is a registered Danfoss trademark
Function:
NOTE!
This parameter is active only
when8-01 Control Site is set to [0] Digital
and control word.
Activates the set-up selection via a digital input.
Activates the set-up selection via the serial
communication port.
Activates the set-up selection via the serial
communication port, AND additionally via one of
the digital inputs.
Activate the set-up selection via the serial
communication port OR via one of the digital
inputs.
Function:
Select control of the adjustable frequency drive
Preset Reference selection via the terminals
(digital input) and/or via the serial communi-
cation port.
Activates Preset Reference selection via a digital
input.
Activates Preset Reference selection via the
serial communication port.
Activates Preset Reference selection via the
serial communication port, AND additionally via
one of the digital inputs.
Activates the Preset Reference selection via the
serial communication port OR via one of the
digital inputs.
Function:
device.
Function:
the highest address in this network.
Decreasing this value optimizes polling for the
token.