Parameters
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
Function:
[12]
Out of current
Motor current is outside range set in
range
4-50 Warning Current Low and
4-51 Warning Current High.
[13]
Below current,
Motor current is lower than set in
low
4-50 Warning Current Low.
[14]
Above current,
Motor current is higher than set in
high
4-51 Warning Current High.
[16]
Below speed,
low
[17]
Above speed,
high
[19]
Below feedback,
low
[20]
Above feedback,
high
[21]
Thermal warning The thermal warning turns on when the
temperature exceeds the limit in motor,
adjustable frequency drive or thermistor.
[22]
Ready, no
The adjustable frequency drive is ready
thermal warning
for operation and no over-temperature
warning is present.
[23]
Remote, ready,
The adjustable frequency drive is ready
no thermal
for operation in auto mode, and no
warning
over-temperature warning is present.
[24]
Ready, Voltage
The adjustable frequency drive is ready
OK
for operation and AC line voltage is
within the specified voltage range.
[25]
Reverse
Motor runs/is ready to run clockwise
when logic = 0 and counter clockwise
when logic = 1. Output changes as soon
as reversing signal is applied.
[26]
Bus OK
Active communication (no timeout) via
serial communication port.
[35]
External Interlock See digital input.
[36]
Control word bit
Bit 11 in the control word controls the
11
relay.
[37]
Control word bit
Bit 12 in control word controls relay.
12
[41]
Below reference,
low
[42]
Above ref, high
[45]
Bus Control
®
VLT
HVAC Basic Drive Programming Guide
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
[60]
[61]
[62]
[63]
[64]
[65]
[70]
[71]
[72]
[73]
[74]
[75]
®
MG18B222 - VLT
is a registered Danfoss trademark
Function:
Comparator 0
See parameter group 13-1*. If
Comparator 0 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
Comparator 1
See parameter group 13-1*. If
Comparator 2 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
Comparator 2
See parameter group 13-1*. If
Comparator 2 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
Comparator 3
See parameter group 13-1*. If
Comparator 3 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
Comparator 4
See parameter group 13-1*. If
Comparator 4 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
Comparator 5
See parameter group 13-1*. If
Comparator 5 is evaluated as TRUE, the
output will go high. Otherwise, it will be
low.
Logic rule 0
See parameter group 13-4*. If Logic
Rule 0 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic rule 1
See parameter group 13-4*. If Logic
Rule 1 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic rule 2
See parameter group 13-4*. If Logic
Rule 2 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic rule 3
See parameter group 13-4*. If Logic
Rule 3 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic rule 4
See parameter group 13-4*. If Logic
Rule 4 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic rule 5
See parameter group 13-4*. If Logic
Rule 5 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
3
3
3-27