Parameters
1-15 Low Speed Filter Time Const
Range:
Size
3
3
related
s]
*
1-16 High Speed Filter Time Const
Range:
Size
related
s]
*
1-17 Voltage filter time const
Range:
Size
related
s]
*

3.2.5 1-2* Motor Data

Parameter group 1-2* comprises input data from the
nameplate on the connected motor.
NOTE!
Changing the value of these parameters affects the setting
of other parameters.
1-20 Motor Power
Range:
[2]
0.12 kW - 0.16 hp
[3]
0.18 kW - 0.25 hp
[4]
0.25 kW - 0.33 hp
[5]
0.37 kW - 0.5 hp
[6]
0.55 kW - 0.75 hp
[7]
0.75 kW - 1 hp
[8]
1.1 kW - 1 hp
3-8
Function:
[ 0.01 - 20
High pass-filter damping time
constant determines the response
time to load steps. Obtain quick
control through a short damping time
constant. However, if this value is too
short, the control becomes unstable.
This time constant is used below 10%
rated speed.
Function:
[ 0.01 - 20
High pass-filter damping time
constant determines the response
time to load steps. Obtain quick
control through a short damping time
constant. However, if this value is too
short, the control becomes unstable.
This time constant is used above 10%
rated speed.
Function:
[ 0.01 - 1
Machine Supply Voltage Filter Time
constant is used for reducing the
influence of high frequency ripples and
system resonances in the calculation of
machine supply voltage. Without this
filter, the ripples in the currents can
distort the calculated voltage and
affects the stability of the system.
Function:
MG18B222 - VLT
®
VLT
HVAC Basic Drive Programming Guide
1-20 Motor Power
Range:
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[19]
[20]
[21]
[22]
[23]
[24]
[25]
[26]
1-22 Motor Voltage
Range:
Size
related
*
®
is a registered Danfoss trademark
1.5 kW - 2 hp
2.2 kW - 3 hp
3 kW - 4 hp
3.7 kW - 5 hp
4 kW - 5.4 hp
5.5 kW - 7.5 hp
7.5 kW - 10 hp
11 kW - 15 hp
15 kW - 20 hp
18.5 kW - 25 hp
22 kW - 30 hp
30 kW - 40 hp
37 kW - 50 hp
45 kW - 60 hp
55 kW - 75 hp
75 kW - 100 hp
90 kW - 120 hp
110 kW - 150 hp
Function:
[ 50.0 -
Enter the nominal motor voltage
1000.0 V]
according to the motor nameplate
data. The default value corresponds to
the nominal rated output of the unit.
This parameter cannot be adjusted
while the motor is running.