Parameters
3
3
The setting options below are all related to the Cascade
Controller.
Wiring diagrams and settings for parameter, see parameter
group 25-** for more details.
[200] Full
Capacity
[201] Pump1
Running
[202] Pump2
Running
[203] Pump3
Running
Setting in parameter
group 5-3*
[200] Pump 1
Running
[201] Pump 2
Running
[203] Pump 3
Running
Table 3.6
5-30 Terminal 27 Digital Output
Option:
[0]
No operation Same options and functions as parameter
*
5-31 Terminal 29 Digital Output
Option:
[0]
No operation Same options and functions as parameter
*
3-26
®
VLT
CAUTION
If the Drive Bypass Function is
enabled, the adjustable frequency
drives are no longer Safety Certified
(for using the Safe Stop in versions
where included).
All pumps running and at full speed
One or more of the pumps controlled by the
Cascade Controller are running. The function
will also depend on the setting of in
25-06 Number Of Pumps. If set to [0] No, Pump
1 refers to the pump controlled by relay
RELAY1, etc. If set to [1] Yes, Pump 1 refers to
the pump controlled by the adjustable
frequency drive only (without any of the built-
in relays involved) and Pump 2 to the pump
controlled by the relay RELAY1. See Table 3.6:
See [201]
See [201]
Setting in 25-06 Number Of Pumps
[0] No
[1] Yes
Controlled by
Adjustable
RELAY1
Frequency Drive
controlled
Controlled by
Controlled by
RELAY2
RELAY1
Controlled by
Controlled by
RELAY3
RELAY2
Function:
group 5-3*.
Function:
group 5-3*.
MG18B222 - VLT
HVAC Basic Drive Programming Guide
5-33 Term X30/7 Digi Out (MCB 101)
Option:
[0]
No operation This parameter is active when option module
*
5-34 On delay, Terminal 42 Digital Output
Range:
0.01s
*
5-35 Off delay, Terminal 42 Digital Output
Range:
0.01 s
*

3.6.4 5-4* Relays

Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
[0]
No operation
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/
remote control
[4]
Standby / no
warning
[5]
Drive running
[6]
Running / no
warning
[7]
Run in range/no
warning
[8]
Run on ref/no
warning
[9]
Alarm
[10]
Alarm or
warning
®
is a registered Danfoss trademark
Function:
MCB 101 is mounted in the adjustable
frequency drive. Same options and functions
as parameter group 5-3*.
Function:
[0.00–600.00s]
Function:
[0.00–600.00 s]
Function:
Default for both relays
The control board receives supply
voltage.
The adjustable frequency drive is ready
for operation and applies supply the
signal on the control board.
The adjustable frequency drive is ready
for operation in Auto On mode.
The adjustable frequency drive is ready
for operation. No start or stop
command is given. No warnings are
present.
Motor is running.
Motor runs, and no warning are present.
Motor runs within programmed current
ranges, see 4-50 Warning Current Low
and 4-51 Warning Current High. No
warnings are present.
Motor runs at reference speed and with
no warnings.
An alarm activates output.
An alarm or warning activates output.