Parameters

3.7.5 6-9* Analog/Digital Output 42

Parameters for configuring the limits for analog/digital
output Terminal 42. Analog outputs are current outputs:
3
3
0/4-20 mA. Resolution on analog outputs is 12 bit. Analog
output terminals can also be set up for digital output.
6-90 Terminal 42 Mode
Option:
[0]
0-20 mA
*
[1]
4-20 mA
[2]
Digital Output
6-91 Terminal 42 Analog Output
Option:
[0]
No operation
[100] Output frequency 0–100 Hz
[101] Reference
[102] Feedback
[103] Motor Current
[106] Power
[139] Bus Control
6-92 Terminal 42 Digital Output
Option:
[0]
No operation
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/remote control
[4]
Standby / no warning
[5]
Drive running
[6]
Running / no warning
[7]
Run in range/no warning
[8]
Run on ref/no warning
[9]
Alarm
[10]
Alarm or warning
[12]
Out of current range
3-34
®
VLT
HVAC Basic Drive Programming Guide
Function:
Set Terminal 42 to act as analog output or
as digital output.
Function:
Select the function of Terminal 42 as an
analog current output. See also
6-90 Terminal 42 Mode.
MinRef. - MaxRef.
MinFB - MaxFB
0-I
max
0-P
nom
0–100%
Function:
Select the function of
Terminal 42 as an
analog current output.
See also 6-90 Terminal
42 Mode. See
5-40 Function Relay for
description of the
choices.
MG18B222 - VLT
6-92 Terminal 42 Digital Output
Option:
[13]
Below current, low
[14]
Above current, high
[16]
Below speed, low
[17]
Above speed, high
[19]
Below feedback, low
[20]
Above feedback, high
[21]
Thermal warning
[22]
Ready, no thermal warning
[23]
Remote, ready, no thermal warning
[24]
Ready, Voltage OK
[25]
Reverse
[26]
Bus OK
[35]
External Interlock
[36]
Control word bit 11
[37]
Control word bit 12
[41]
Below reference, low
[42]
Above ref, high
[45]
Bus Control
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[193] Sleep Mode
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
6-93 Terminal 42 Output Min Scale
Range:
0 %
[0 - 200 %]
*
®
is a registered Danfoss trademark