Parameters
16-62 Analog Input AI53
Range:
1
[0 - 20 ]
*
3
3
16-63 Terminal 54 Setting
Option:
[0] Current mode
[1] Voltage mode
16-64 Analog Input AI54
Range:
1
[0 - 20 ]
*
16-65 Analog Output AO42 [mA]
Range:
0 mA
[0 - 20 mA] View the actual value at output 42 in mA.
*
16-66 Digital Output
Range:
0
[0 -
View the binary value of all digital outputs.
*
15 ]
Definition:
X: Not used
0: Low
1: High
16-67 Pulse Input #29 [Hz]
Range:
0
[0 - 130000 ] View the actual frequency rate on terminal
*
3-56
Function:
View the actual value at input 53.
Function:
View the setting of input terminal 54. Current
= 0; Voltage = 1.
Function:
View the actual value at input 54.
Function:
The value shown reflects the selection in
6-90 Terminal 42 Mode and 6-91 Terminal 42
Analog Output.
Function:
XX
None used
X0
Terminal 42 not used, Terminal 45
low
X1
Terminal 42 not used, Terminal 45
High
0X
Terminal 42 low, Terminal 45 not
used
0
Terminal 42 low, Terminal 45 low
1
Terminal 42 low, Terminal 45 high
1X
Terminal 42 high, Terminal 45 not
used
10
Terminal 42 high, Terminal 45 low
11
Terminal 42 high, Terminal 45 high
Table 3.11
Function:
29.
MG18B222 - VLT
®
VLT
HVAC Basic Drive Programming Guide
16-71 Relay Output [bin]
Range:
0
[0 - 65535 ] View the setting of the relay.
*
16-72 Counter A
Range:
0
[-32768 -
*
32767 ]
®
is a registered Danfoss trademark
Function:
Bits definition:
Bit 0~2
Unused
Bit 3
Relay 02
Bit 4
Relay 01
Bit 5~15
Unused
Table 3.12
Function:
View the present value of Counter A. Counters
are useful as comparator operands, see
13-10 Comparator Operand.
The value can be reset or changed either via
digital inputs (parameter group 5-1*) or by
using an SLC action (13-52 SL Controller Action).