Danfoss VLT HVAC Basic Drive FC 100 Series Programming Manual page 57

Hide thumbs Also See for VLT HVAC Basic Drive FC 100 Series:
Table of Contents

Advertisement

Parameters
Selected
Event
Relay
output
On Delay
P 5-41
Selected
Event
Relay
output
On Delay
P 5-41
Figure 3.7
5-42 Off Delay, Relay
Array[2]: Relay1[0], Relay2[1]
Range:
Function:
0.01 s
[0.01 - 600.00
Enter the delay of the relay cut-out
*
s]
time. Select one of available
mechanical relays and MCB 105 in an
array function. See 5-40 Function Relay.
Selected
Event
Relay
output
On Delay
P 5-41
Figure 3.8
If the selected event condition changes before the on or
off delay timer expires, the relay output is unaffected.
3.6.5 5-5* Pulse Input
The pulse input parameters are used to define an
appropriate window for the impulse reference area by
configuring the scaling and filter settings for the pulse
inputs. Input terminals 29 or 33 act as frequency reference
inputs. Set terminal 29 (5-13 Terminal 29 Digital Input) or
terminal 33 (5-15 Terminal 33 Digital Input) to [32] Pulse
input. If terminal 29 is used as an input, then set
5-01 Terminal 27 Mode to [0] Input.
®
VLT
HVAC Basic Drive Programming Guide
O Delay
P 5-42
O Delay
P 5-42
®
MG18B222 - VLT
is a registered Danfoss trademark
Ref.
(RPM)
High
ref.
value
P 5-53/
p 5-58
Low
ref.
value
P 5-52/
p 5-57
Low freq.
P 5-50/
P 5-55
Figure 3.9
5-50 Term. 29 Low Frequency
Range:
Function:
100 Hz
[0 - 110000
Enter the low frequency limit
*
Hz]
corresponding to the low motor shaft
speed (i.e. low reference value) in
5-52 Term. 29 Low Ref./Feedb. Value. Refer
to the diagram in this section.
This parameter is available for only.
5-51 Term. 29 High Frequency
Range:
Function:
100 Hz
[0 - 110000
Enter the high frequency limit
*
Hz]
corresponding to the high motor shaft
speed (i.e. high reference value) in
5-53 Term. 29 High Ref./Feedb. Value.
This parameter is available for only.
5-52 Term. 29 Low Ref./Feedb. Value
Range:
0.000 Reference-
[-999999.999 -
FeedbackUnit
999999.999
*
ReferenceFeed-
backUnit]
3
High freq.
Input
P 5-51/
(Hz)
P 5-56
Function:
Enter the low reference
value limit for the motor
shaft speed [RPM]. This is
also the lowest feedback
value, see also 5-57 Term.
33 Low Ref./Feedb. Value.
Set terminal 29 to digital
input (5-02 Terminal 29
Mode =input [0] (default)
and 5-13 Terminal 29
Digital Input = applicable
value).
This parameter is
available for only.
3-29
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents