Parameter list
4.5.4

Analogue output 1

Code
Parameter
P2.5.4.1
Iout 1 signal
P2.5.4.2
Iout Content
Iout Filter
P2.5.4.3
Time
P2.5.4.4
Iout Invert
Iout
P2.5.4.5
Minimum
P2.5.4.6
Iout Scale
P2.5.4.7
Iout Offset
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
Table 18.
Analogue output signals, G2.3.4
Min
Max
AnOUT:0.1
AnOUT:E.10
0
11
0
10
0
1
0
1
10
1000
-100
100
Unit
Default
ID
AnOUT:A.1
464
1 / O/P
307
Freq
s
1
308
0 / No
309
Inversion
0 / 0 mA
310
%
100
311
%
0
375
vacon · 43
Description
Connect the AO1 signal to
the analogue output of your
choice with this parameter.
0 =Not used
1 = DC Voltage
2 = Drive Current
3 = Output Voltage
4 = Active Current
5 = Power
6 = Reactive Current
7 = Power Bidirectional
8 = AI1
9 = AI2
10 = FB Analogue Output
11 = Line Voltage
12 = FreqOut, bidirectional
13 = Value Control Out
0 = No filtering
0 = Not inverted
1 = Inverted
0 = 0 mA
1 = 4 mA
Percentage multiplier.
Defines output when
content is in maximum
value
Add -1000 to 1000% to the
analogue output.
4