Analogue Output 2 - Danfoss Vacon NXP Applications Manual

Grid converter. ac drives
Hide thumbs Also See for Vacon NXP:
Table of Contents

Advertisement

44 · vacon
4.5.5

Analogue output 2

Code
Parameter
P2.5.5.1
Iout 2 signal
P2.5.5.2
Iout Content
Iout Filter
P2.5.5.3
P2.5.5.4
Iout Invert
P2.5.5.5
Minimum
P2.5.5.6
Iout Scale
P2.5.5.7
Iout Offset
4
Table 19.
Min
AnOUT:0.1
AnOUT:E.10
0
0
Time
0
Iout
0
10
-100
Analogue output signals, G2.3.4
Max
Unit
Default
AnOUT:A.1
1 / O/P
11
Freq
10
s
1
0 / No
1
Inversion
1
0 / 0 mA
1000
%
100
100
%
0
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
Parameter list
ID
Description
Connect the AO1 signal to
464
the analogue output of your
choice with this parameter.
0 = Not used
1 = DC Voltage
2 = Drive Current
3 = Output Voltage
4 = Active Current
5 = Power
6 = Reactive Current
307
7 = Power Bidirectional
8 = AI1
9 = AI2
10 = FB Analogue Output
11 = Line Voltage
12 = FreqOut, bidirectional
13 = Value Control Out
308
0 = No filtering
0 = Not inverted
309
1 = Inverted
0 = 0 mA
310
1 = 4 mA
Percentage multiplier.
Defines output when
311
content is in maximum
value
Add -1000 to 1000% to the
375
analogue output.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents