Keypad control parameters

6. Keypad control parameters
Unlike the parameters listed above, these parameters are located in the M3 menu of the control
panel. The reference parameters do not have an ID number.
P3.1
Control Place
The active control place can be changed with this parameter. PC Control place can be
only activated when from NCDrive when this parameter is set 2 / Keypad.
0 = PC Control, Activated by NCDrive
1 = I/O terminal
2 = Keypad
3 = Fieldbus
4 = SystemBus
On keypad control pressing Stop button more than a 2 second will open the MCB.
P3.2
License Key
Enter the licence key.
The standard AFE functions are available without a licence key. A licence key is not
necessary for the frame FR4.
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
ID125
"Control Place"
ID1995
"License Key"