Fault codes
F9
Undervoltage fault
DC link voltage is below the fault voltage limit of the drive.
S1 = DC link too low during the run.
S2 = No data from the power unit.
S3 = Undervoltage control supervision.
Possible cause
-
Too low a supply voltage.
-
AC drive internal fault.
-
One of the input fuses is broken.
-
External charge switch has not been closed.
Correcting measures
-
In case of temporary supply voltage break, reset the fault and restart the AC drive.
-
Check supply voltage.
-
Check the operation of the DC charge.
-
Contact your local distributor.
F10
Line Synchronization Fault
S1 = Phase supervision diode supply.
S2 = Phase supervision active front end.
S3 = Grid Converter operation, frequency outside frequency limits (G2.6.3).
Possible cause:
-
Input line phase is missing.
-
No grid to be synchronized
-
Slow power increase in a grid and limit controllers has activated.
-
Power or current limits too low for the active load.
Correcting measures
-
Check supply voltage, fuses and cable.
-
Check drive dimensioning against grid power requirements.
-
Check that power or current limits are sufficient.
F11
Line phase supervision
Possible cause:
-
Current measurement has detected that there is no current in one phase, or one phase
current is considerably different from other phases.
Correcting measures
-
Check the motor cable and the motor.