Monitoring signals
V1.1.9
Status Word (Application)
The Application Status Word combines different statuses of the drive to one data word.
b0
b1
Not in Ready state
b2
Not Running
b3
No Fault
b4
b5
Quick stop active
b6
Run Disabled
b7
No Warning
b8
b9
b10
b11
b12
No Run Request
b13
b14
b15
V1.1.10
Supply Frequency
The drive output frequency. Updated in the STOP state when Regen Option B9 is
activated.
V1.1.11
Supply Voltage V
The drive output voltage.
V1.1.12
Line Frequency D7
The measured line voltage frequency when using the OPT-D7 option board in slot C.
When the OPT-D7 board is not used, it is possible to use Analogue Input 3 and 4 ID write
function to give the grid the Line Frequency and Line Voltage. This enables use of grid PI
voltage controller without the OPT-D7 board. Note that both line frequency and line
voltages needs to be given. By activating Control Options 2 B2 these analogue inputs can
be used also to grid protection.
V1.1.13
Line Voltage D7 V
The measured line voltage rms value when using the OPT-D7 option board in slot C.
When the OPT-D7 board is not used, it is possible to use Analogue Input 3 and 4 ID write
function to give the grid the Line Frequency and Line Voltage. This enables use of grid PI
voltage controller without the OPT-D7 board. Note that both line frequency and line
voltages needs to be given. By activating Control Options 2 B2 these analogue inputs can
be used also to grid protection.
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
ID 43
Status Word (Application) ID43
FALSE
Ready
Running
Fault
Quick stop not active
Run Enable
Warning
Charging Switch closed (internal)
MCB Control
MCB Feedback
Run Request
At Current Limit
Island Mode Active
uGrid Mode Active
Hz
ID 1
ID 1107
Hz
ID 1654
ID 1650