Description of parameters
if 100% of Base Current Reference is given, the drive will feed 100% power to the grid.
The situation is the same with the frequency reference set to 52 Hz and with 2.000 Hz
drooping.
Base current reference can be used together with selection
StartPowerMode: Isochron.Gen. This selection will keep the drive frequency reference
same as the grid frequency, and the power that is fed or taken from the drive is solely
defined by the Base Current Reference parameter.
Freq.
52,0 Hz
51,5 Hz
51,0 Hz
50,5 Hz
50,0 Hz
49,5 Hz
49,0 Hz
48,5 Hz
48,0 Hz
2.2.4.7
Base Reference Ramp Rate
This parameter defines the increase rate of the base current reference when the
reference is changed or the drive is started.
110 %
10 %
2.2.4.8
Base Reference to Zero
This parameter defines in which situations Base Current Reference is set to the value of
P2.2.6.8 BaseRefAtStop.
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
Change
+4%
+3%
+2%
+1
%
25%
-1%
-2%
-3%
-4%
Figure 15.
ID1536
Current
Reference
Input Ref.
2 s
Figure 16.
ID1537
3
of P2.11.5
50%
75%
100%
Internal Ref
50 % / s
vacon · 63