Fault codes
F67
Fieldbus communication fault on slot E
Possible cause:
-
The data connection between the fieldbus Master and the fieldbus board is broken.
-
Watchdog pulse is missing from PLC, if Control Slot Selector is 0, or set for slot E.
Correcting measures:
-
Check installation.
-
If installation is correct contact your local distributor.
F68
D7 Voltage or frequency fault
This monitors Grid frequency and voltage for synchronization function.
Possible cause:
-
OPT-D7 measurements are not within limits.
F69
OPT-D7 Missing
OPT-D7 board is not present for the function that is requested.
Possible cause:
Correcting measures:
F70
Supply Voltage
Supply voltage is not inside of set hysteresis. Not to be confused with OPT-D7 protections.
F71
LCL Temperature
LCL Temperature has reached the warning limit.
Possible cause:
Correcting measures:
F72
License
Licence has not been given or licence key is wrong
Possible cause:
Correcting measures:
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com