104 · vacon
2.10.10
FB Data In 1 Sel
2.10.11
FB Data In 2 Sel
2.10.12
FB Data In 3 Sel
2.10.13
FB Data In 4 Sel
2.10.14
FB Data In 5 Sel
2.10.15
FB Data In 6 Sel
2.10.16
FB Data In 7 Sel
2.10.17
FB Data In 8 Sel
Using these parameters, you can control any parameter value from the fieldbus. Enter
the ID number of the item you wish to control as the value of these parameters.
2.10.18
GSW Data
With this parameter it is possible to select which data is sent in FBGeneralStatusWord.
2.10.19
State Machine
The application provides a possibility to select what kind of state machine is used.
0: Basic
This mode makes fieldbus control behave as is explained in the fieldbus board manual.
1: Standard
A simple control word that is used in modes where the control word from fieldbus is
used as such. For some fieldbus boards this requires a bypass operation.
2: Vacon AFE 1
This mode uses a ProfiDrive type state machine in the application level. You can use this
mode on fieldbus boards that do not have a state machine or have a possibility to bypass
the state machine function in the option board.
2.10.20
FB Ref Min
2.10.21
FB Ref Max
The minimum and maximum limits for fieldbus DC Voltage Reference.
2.10.22 Control Slot selector
This parameter defines which slot is used as the main control place when two fieldbus
boards have been installed in the drive.
0 = All slots. Control signals are monitored from every fieldbus board.
4 = Slot D. Control signals are monitored from Slot D.
5 = Slot E. Control signals are monitored from Slot E.
5
ID1440
"ControlSlotSel."
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
Description of parameters