Control I/O
2. Control I/O
OPT-A1
Terminal
1
+10V
2
AI1+
3
AI1-
4
AI2+
5
AI2-
6
+24V
7
GND
8
DIN1
9
DIN2
10
DIN3
11
CMA
12
+24V
13
GND
14
DIN4
15
DIN5
16
DIN6
17
CMB
18
AO1+
19
AO1-
20
DO1
OPT-A2
21
RO1
22
RO1
23
RO1
24
RO2
25
RO2
26
RO2
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
Table 1. Minimum recommended I/O configuration.
Signal
Reference voltage output
ref
Analogue input 1.
Range 0-10V, R
= 200Ω
i
Range 0-20 mA R
= 250Ω
i
I/O Ground
Analogue input 2.
Range 0-10V, R
= 200Ω
i
Range 0-20 mA R
= 250Ω
i
Control voltage output
I/O ground
Programmable G2.2.1
Programmable G2.2.1
Programmable G2.2.1
Common for DIN 1– DIN 3
Control voltage output
I/O ground
MCB Feedback
Programmable G2.2.1
Quick Stop
Programmable G2.2.1
Programmable G2.2.1
Common for DIN4– DIN6
Analogue output 1
Digital output
READY
Relay output 1
Programmable P2.3.1.2
Relay output 2
MCB control
Description
Voltage for potentiometer, etc.
Input range selected by jumpers.
Default range: Voltage 0 – 10 V
Ground for reference and controls
Input range selected by jumpers.
Default range: Current 0 – 20 mA
Voltage for switches, etc. max 0.1 A
Ground for reference and controls
Connect to GND or +24V
Voltage for switches (see #6)
Ground for reference and controls
0 = MCB open
1 = MCB closed
0 = Quick Stop Active
1 = No Quick Stop
Connect to GND or +24V
Programmable
Range 0– 20 mA/R
, max. 500Ω
L
Programmable P2.3.1.1
Open collector, I≤50mA, U≤48 VDC
Switching capacity
24 VDC / 8 A
250 VAC / 8A
125 VDC / 0.4 A
This RO is not programmable.
Fixed for MCB Control (Close)
vacon · 19
2
Need help?
Do you have a question about the Vacon NXP and is the answer not in the manual?
Questions and answers