Fieldbus Monitoring Values - Danfoss Vacon NXP Applications Manual

Grid converter. ac drives
Hide thumbs Also See for Vacon NXP:
Table of Contents

Advertisement

26 · vacon
3.2.3

Fieldbus monitoring values

V1.3.1
FB Control Word
The control word from fieldbus. The table below is for "2 / Vacon AFE 1" Selection
(P2.10.19) in bypass operation for such fieldbus board that natively supports this or can
be parameterised to bypass mode. See other profile selections from chapter Status and
Control Word.
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
3
ID 1160
FB Control Word ID1160
Signal
0 = Open MCB.
DC Charge
1 = Close DC charge contactor, MCB closed automatically.
0 = Stop Command
Start
1 = Start Command
Reset
0>1 Reset fault.
Fieldbus
0 = No control from fieldbus
Control
1 = Control from fieldbus
0>1>0>1...0.5 s square wave clock. This is used to check data
Watchdog
communication between the fieldbus master and the drive.
Can be used to control RO or the parameter directly by ID
FB DIN2
number. G2.4.1
Can be used to control RO or the parameter directly by ID
FB DIN3
number. G2.4.1
Can be used to control RO or the parameter directly by ID
FB DIN4
number. G2.4.1
Comment