ID.Bit Free DO
2.5.3.5
ID.Bit Free DO
Select the signal for controlling the DO. The parameter must be set in the format xxxx.yy
where xxxx is the ID number of a signal and yy is the bit number. For example, the value
for DO control is
is ON when the bit number 02 of the warning word (ID no. 1174), that is,
is high.
5.5.3
Analogue output 1 & 2 & 3
2.5.4.1
Iout 1 signal
2.5.5.1
Iout 2 signal
2.5.6.1
Iout 3 signal
Connect the AO signal to the analogue output of your choice with this parameter.
2.5.4.2
Iout 1 Content
2.5.5.2
Iout 2 Content
2.5.6.2
Iout 3 Content
0 = Not used
1 = DC Voltage
Scaling: 500 Vac Unit 0-1000 Vac, 690 Vac Unit 0-1317 Vdc
2 = Drive Current
Scaled to Nominal Current
3 = Output Voltage
Scaled to Nominal Voltage
4 = Active Current
Scaled to 100 %.
5 = Power
Scaled to 100 %
6 = Reactive Current
Scaled to 100 %
7 = Power Bidirectional
Scaled to -200 % to 200 %
8 = AI1
9 = AI2
10 = FB Analogue Output
11 = LineVoltage
Scaled to Nominal Voltage.
12 = FreqOut, bidirectional
13 = Control Value output
5
1174.02
. 1174 is the ID number of Warning Word 1. So the digital output
Description of parameters