Description of parameters
2.9.9.4
Over Load Maximum Step
Step in the over load counter when the input value is at maximum input level defined by
P2.9.9.3.
2.9.10
Fault Simulation
With this parameter it is possible to simulate different faults without actually making, for
example, an over current situation. In the point of view of the drive interface, the
operation is identical to actual fault situation.
B00 = +1 = Simulates an over current fault (F1)
B01 = +2 = Simulates an over voltage fault (F2)
B02 = +4 = Simulates an under voltage fault (F9)
B03 = +8 = Simulates an output phase supervision fault (F11)
B04 = +16 = Simulates an earth fault (F3)
B05 = +32 = Simulates a system fault (F8)
This fault simulation covers a wide range of different faults in drive. See the fault
description for details.
B06 = +64 = Free
B07 = +128 = Simulates an over temperature warning (W14)
B08 = +256 = Simulates an over temperature fault (F14)
The warning bit must be active for a fault to appear in simulation. If the fault bit is left
active, the drive will go FAULT state at warning limit when the drive temperature
rises to the warning level.
B09 = +512 = Reserved
5.10

Fieldbus

2.10.1
FB Actual Value Sel
2.10.2
FB Data Out1 Sel
2.10.3
FB Data Out2 Sel
2.10.4
FB Data Out3 Sel
2.10.5
FB Data Out4 Sel
2.10.6
FB Data Out5 Sel
2.10.7
FB Data Out6 Sel
2.10.8
FB Data Out7 Sel
2.10.9
FB Data Out8 Sel
Using these parameters, you can monitor any monitoring or parameter value from the
fieldbus. Enter the ID number of the item you wish to monitor as the value of these
parameters.
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
ID1840
"OverLoadMaxStep"
ID1569
"Fault Simulation"
vacon · 103