Advertisement

Description of parameters
P2.9.6.2
Voltage Low Warning Limit
Low limit for a warning indication. A percentage value from a set supply voltage
parameter.
P2.9.6.3
Voltage Low Trip Limit
Low limit for a fault indication. A percentage value from a set supply voltage parameter.
The common tripping limit of the land based grid code standard is 80 % of Un within 200
ms.
P2.9.6.4
Voltage High Warning Limit
High limit for a warning indication. A percentage value from a set supply voltage
parameter.
P2.9.6.5
Voltage High Trip Limit
High limit for a fault indication. A percentage value from a set supply voltage parameter.
The common tripping limit of the land based grid code standard is 115 % of Un within 200
ms.
P2.9.6.6
Voltage Trip Delay
Delay to a fault when the voltage has exceeded the fault levels.
5.9.7

Grid frequency

A monitoring function for the drive output frequency and the measured frequency from OPT-D7.
Will also trip this when operating in pure AFE mode.
NOTE: This functionality is not Grid Code functionality even if functionality may be similar.
P
FreqHighTripLim
P
FreqHighWarnLim
P
Supply Frequency
P
FreqLowWarnLim
P
FreqLowTripLim
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
ID1893
ID1899
ID1895
ID1799
ID1898
OPT-D7 Grid Freq. D7
Fault: F93 D7 Frequency
P
Freq. Trip Delay
P
Freq. Trip Delay
Figure 38.