Danfoss Vacon NXP Applications Manual page 78

Grid converter. ac drives
Hide thumbs Also See for Vacon NXP:
Table of Contents

Advertisement

76 · vacon
2.5.1.13
Charge control
When this is activated, the drive will start charging of DC from the start command and go
directly to RUN state. The charging starts from the start command.
2.5.1.14
Common alarm
Drive has a warning active. This indication needs to be reset separately even if the
situation is over.
2.5.1.15
Ready For Start
The drive has no interlock for starting the charging and going to RUN state.
2.5.1.16
Quick Stop Active
The drive has received a quick stop command.
5.5.1.1
Fieldbus digital inputs connection
P2.5.1.17 Fieldbus input data 1
P2.5.1.19 Fieldbus input data 2
P2.5.1.21 Fieldbus input data 3
P2.5.1.23 Fieldbus input data 4
The data from the fieldbus main control word can be led to the digital outputs of the
drive. See the fieldbus board manual for the location of these bits.
P2.5.1.18 Fieldbus digital input 1 parameter
P2.5.1.20 Fieldbus digital input 2 parameter
P2.5.1.22 Fieldbus digital input 3 parameter
P2.5.1.24 Fieldbus digital input 4 parameter
With these parameters you can define the parameter to be controlled by using FB digital
input.
Example:
All option board inputs are already in use, but you want to give a DI: DC Brake Command
(ID416). You also have a fieldbus board in the drive.
Set parameter ID891 (Fieldbus Digital Input 1) to
braking command from the fieldbus by Profibus control word (bit 11).
It is possible to control any parameter in the same way if values 0 = FALSE and 1 = TRUE
are significant for that parameter. For example, P2.6.5.3 Brake Chopper (ID504) can be
switched on and off using this function (Brake Chopper: 0 = Not Used, 1 = On, Run).
5
ID455 "FB Dig Input 1"
ID456 "FB Dig Input 2"
ID457 "FB Dig Input 3"
ID169 "FB Dig Input 4"
ID891 "FB Dig 1 Par ID"
ID892 "FB Dig 2 Par ID"
ID893 "FB Dig 3 Par ID"
ID894 "FB Dig 4 Par ID"
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
Description of parameters
416
. Now you are able to control DC