Control Terminals - Danfoss VLT Micro FC 51 Quick Manual

Hide thumbs Also See for VLT Micro FC 51:
Table of Contents

Advertisement

Quick Guide for VLT Micro FC 51
1.3.6 Connecting to Mains and Motor
The frequency converter is designed to operate all standard three-phased asynchronous motors.
The frequency converter is designed to accept mains/motor cables with a maximum cross-section of 4 mm
(M1, M2 and M3) and maximum cross-section 16 mm
Use a shielded/armored motor cable to comply with EMC emission specifications, and connect this cable to
both the decoupling plate and the motor metal.
Keep motor cable as short as possible to reduce the noise level and leakage currents.
For further details on mounting of the decoupling plate, please see instruction MI.02.BX.YY.
Also see EMC-Correct Installation in Operating Instruction MG.02.AX.YY.
Step 1: First, mount the earth wires to earth terminal.
Step 2: Connect motor to terminals U, V and W.
Step 3: Mount mains supply to terminals L1/L, L2 and
L3/N (3-phase) or L1/L and L3/N (single-phase) and
tighten.

1.3.7 Control Terminals

All control cable terminals are located underneath the
terminal cover in front of the frequency converter. Re-
move the terminal cover using a screwdriver.
See back of terminal cover for outlines of
control terminals and switches.
Do not operate switches with power on the
frequency converter.
Parameter 6-19 must be set according to
Switch 4 position.
Switch 1:
*OFF = PNP terminals 29
ON = NPN terminals 29
Switch 2:
*OFF = PNP terminal 18, 19, 27 and 33
ON = NPN terminal 18, 19, 27 and 33
Switch 3:
No function
Switch 4:
*OFF = Terminal 53 0 - 10 V
ON = Terminal 53 0/4 - 20 mA
* = default setting
Table 1.4: Settings for S200 Switches 1-4
2
/6 AWG (M4 and M5).
Illustration 1.2: Mounting of earth cable, mains and motor
wires.
Illustration 1.3: Removing terminal cover.
Illustration 1.4: S200 Switches 1-4.
®
MG.02.B5.02 - VLT
is a registered Danfoss trademark
1 Quick Guide
1
2
/10 AWG
5