Operation Together With Sunny Boys - SMA Sunny Island 2012 Technical Description

Stand-alone grid inverter
Table of Contents

Advertisement

Connecting External Sources

13.2.8 Operation Together With Sunny Boys

Since electricity is fed into the grid through the relay of the Sunny Island, it must be prevented from
overloading. For this reason, reverse power monitoring is used which, if required, disconnects the
main power grid if the reverse power limit is exceeded or an excessive load is applied to the relay.
NOTICE!
If the current flowing through the relay exceeds the maximum permissible current, the grid
is disconnected (relay protection). The quantity of PV output installed in the stand-alone
grid must not exceed the maximum quantity allowed by the AC input (see section 20
"Technical Data" (Page 197)).
If the battery is fully charged, the frequency limits the power output of the AC feed-in generators
(Sunny Boys) in the stand-alone grid. If the grid is now reconnected, the frequency would be
lowered, if required, as the Sunny Island is synchronized with the grid. The AC feed-in generators
(Sunny Boys) would then feed additional energy into the system and possibly overload the batteries.
In order to prevent this, in this case the stand-alone grid frequency is temporarily increased
("231.04 AcSrcFrqDel" parameter), in line with the synchronization, until the AC feed-in generators
(Sunny Boys) are disconnected from the stand-alone grid as a result of the grid limits being
exceeded.
150
SI2012_2224-TEN082311
SMA Solar Technology AG
Technical Description