10.3.3 Accessing Parameters Directly

Under the menu "600# Direct Access" it is possible to directly access selected parameters via their
name or number.
Via the Select Name submenu, you have direct access to the following functions:
ManChargSel: manual starting of equalization charge (see section 12.4.3 "Equalization
Charge" (Page 126))
Under the menu "Select Number" each parameter can be directly accessed by entering the
parameter number.
Example
Using the menu 600# Direct Access, you can select the "222.01 BatChrgCurMax"
parameter, for example, to set the maximum battery charging current.
The direct access must be entered as a five-digit number, for example, 22201. Here, the
first three digits describe the menu number and the last two describe the parameter
number.
After the parameter has been set successfully, exit the this menu level.

10.3.4 Meter Compact

The "150# Meter Compact" menu should, above all, facilitate the commissioning for the installer.
The display delivers information on the following items at a glance:
Battery
Inverter (AC values)
grid/generator (external)
Inverter status
Select item
You can select among the various items within the Meter Compact by turning the
pushbutton right or left.
Exit the menu by pressing the pushbutton.
Technical Description
Operating the Sunny Island
SI2012_2224-TEN082311