(First) Commissioning
8.
Subsequently, check the offset error
"120.06 TotBatCur" should be (close to) zero
9.
Switch off the Sunny Island and remove all voltages (see chapter 10.1 "Switching On and
Off" (Page 83)).
10. Connect the "BatCur+" wire to the battery current sensor's terminal clamp 2 again.
Make sure the wires have the correct polarity.
-
BatCur+ to terminal clamp 1
-
BatCur- to terminal clamp 2
11. Start the Sunny Island (see chapter 10.1.1 "Switching On/Starting" (Page 83)).
12. Check the current direction: "120.06 TotBatCur"
Current direction
Battery discharge:
no generator/grid connected
Loads are being supplied
The value of the battery current is positive
Charging the battery
Generator/grid connected
Loads not being/being marginally supplied
Battery is being charged
The value of the battery current is positive
82