SMA Sunny Island 2012 Technical Description page 136

Stand-alone grid inverter
Table of Contents

Advertisement

Connecting External Sources
Generator Interface 233.07 GnSrtMod Manual; Start at the Generator
1
Manual generator start
2
"Generator is running" detected, beginning of
warm-up phase
3
Internal generator request is ignored
4
Warm-up phase is completed, generator is
connected
5
Generator current limiation
6
Current is reduced, battery absorption phase
7
Manual generator stop, disconnection of the
generator
8
Minimum generator stop time has expired
Generator Interface 233.07 GnSrtMod Autostart; Start at the Generator
1
Manual generator start
2
"Generator is running" detected, beginning of
warm-up phase
3
Warm-up phase is completed
4
Generator is connected
5
Generator current limiation
6
Current is reduced, battery absorption phase
7
Manual generator stop, disconnection of the
generator
8
Generator is disconnected, beginning of stop time
9
End of stop time
* Transfer Relay
136
SI2012_2224-TEN082311
2
1
Gn
3
GnReq
4
TrfRel*
ExtCur
Warm-up time
2
3
1
Gn
GnReq
TrfRel*
ExtCur
SMA Solar Technology AG
7
5
6
Stop time
7
4
8
5
6
Technical Description