(First) Commissioning
The following parameters must be set when "New Battery" is selected:
(default setting shown in bold)
-
Battery type: 002#05 BatTyp (VRLA, FLA, NiCd)
-
Battery voltage: 002#06 BatVtgLst (22 V, 24 V in 2 V increments for FLA and VRLA, 21.6
V, 22.8 V, 24 V in 1.2 V increments for NiCd), 24 V Sunny Island 2224, 12 V Sunny
Island 2012
Nominal battery capacity: 002#07 BatCpyNom (100 Ah to 10000 Ah, preset 140 Ah
-
for Sunny Island 2224, )
The following parameters must be set when "New System" is selected:
(default setting shown in bold)
-
System configuration: 003#01 (selection see "Overview of System Configurations:"
(Page 79)), presetting is "1phase 1SI"
-
Voltage / Frequency type: 003#02 AcVtgFrqSet (230V_50Hz, 220V_60Hz)
-
Date: 003#03 Dt (dd.mm.yyyy)
-
Time: 003#04 Tm (hh:mm:ss)
-
Battery type: 003#05 BatTyp (VRLA, FLA, NiCd)
-
Battery voltage: 003#06 BatVtgLst (22 V, 24 V in 2 V increments for FLA and VRLA, 21.6
V, 22.8 V, 24 V in 1.2 V increments for NiCd), 24 V Sunny Island 2224, 12 V Sunny
Island 2012
-
Nominal battery capacity: 003#07 BatCpyNom (50 Ah bis 10000 Ah, 140 Ah)
-
External power supply unit: 003#08 ExtSrc (PvOnly, Gen, Grid, GenGrid)
Maximal grid current: 003#09 GdCurNom (0 to 25 A, 16 A)
-
Maximal generator current: 003#10 GnCurNom (0 to 25 A, 16 A)
-
Generator interface: 003#11 GnStrMod (Manual, GenMan, Autostart)
-
a)
These applications are only possible with firmware versions 3.0 and above.
78
SI2012_2224-TEN082311