SMA Sunny Island 2012 Technical Description page 170

Stand-alone grid inverter
Table of Contents

Advertisement

Parameter List Overview
Menu
Parame
nr.
ter.Nr.
231
09
ExtSrc
232# Grid Control
232
01
GdVtgMin
232
02
GdVtgMax
232
03
GdCurNom
232
04
GdFrqNom
232
05
GdFrqMin
232
06
GdFrqMax
232
07
GdVldTm
232
08
GdMod
232
09
GdRvPwr
232
10
GdRvTm
232
15
GdAISns
233# Gen Control
233
01
GnVtgMin
233
02
GnVtgMax
233
03
GnCurNom
233
04
GnFrqNom
233
05
GnFrqMin
233
06
GnFrqMax
170
SI2012_2224-TEN082311
Parameter Name
Grid
V
V
A
Hz
Hz
Hz
sec
GridCharge
GridFeed
W
sec
Low,
Medium
standard
High
V
V
A
Hz
Hz
Hz
Range/Unit
Default
value
Grid
189
259.5
16
50
47.65
50.15
30
GridCharge
100
5
standard
172.5
264.5
25
50
44.64
60
SMA Solar Technology AG
Description
Grid Operation
Minimum grid voltage
Maximum grid voltage
Nominal grid current
Nominal frequency
Minimum grid frequency
Maximum grid frequency
minimum time required for grid (voltage
and frequency) to be within permissible
range for connection
Grid interface
permissible grid reverse power
(effective power)
permissible time for grid reverse power
AI sensitivity
Min. generator voltage
Max. generator voltage
Nominal generator current
Nominal generator frequency (at
nominal load)
230V_50HZ = 50
220V_60HZ = 60
depending on the setting in QCG
Minimum generator frequency
230V_50HZ = 44.64
220V_60HZ = 50
depending on the setting in QCG
Maximum generator frequency
230V_50HZ = 60
220V_60HZ = 70
depending on the setting in QCG