Connecting External Sources
The following sequence charts provide an overview of the start/stop behavior of the Sunny Island
in the case of automatic generator operation:
Generator Interface 233.07 GnSrtMod Manual; Generator Request Via
Sunny Island
1
Generator is requested via Sunny Island
2
Manual generator start
3
Generator detection on, beginning of warm-up
phase
4
Warm-up phase is comleted, generator is
connected
5
Generator current limiation
6
Minimum operating time has expired
7
Current is reduced, battery absorption phase
8
Charging process is completed, request signal is
disabled
9
Manuel stop of generator
10 Generator is disconnected
11 Stop time has expired
Generator Interface 233.07 GnSrtMod Autostart; Generator Request Via
Sunny Island
1
Generator start by Sunny Island
2
Generator Start
3
Beginning of warm-up time
4
Warm-up time has expired
5
Generator is connected
6
Current limitation
7
Minimum operating time has expired
8
Current is reduced, battery absorption phase
9
Charge process complete, generator disconnected
10 Generator post-run period is completed, generator
is disconnected
11 Stop time has expired
* Transfer Relay
140
SI2012_2224-TEN082311
3
4
Gn
2
1
GnReq
TrfRel*
ExtCur
GnWarmTm
GnRunTmMin
4
3
Gn
2
1
GnReq
5
TrfRel*
ExtCur
Warm-up time
Minimum
SMA Solar Technology AG
6
9
8
10
5
7
GnRunTmMax
7
10
9
8
6
Post run
Stop time
Technical Description
11
11