SMA Sunny Island 2012 Technical Description page 167

Stand-alone grid inverter
Table of Contents

Advertisement

SMA Solar Technology AG
Changes to parameters
The cells with a grey background in the following tables show all menu items that can
only be changed after entering the installer password.
All parameters can be set using a connected PC/laptop with the Sunny Data Control
software, a Sunny WebBox or a Sunny Boy Control (see section 7.5 "Communication"
(Page 53)).
210# Set Inverter
Menu
Parame
nr.
ter Nr.
210
01
InvVtgNom
210
02
InvChrgCurMax
210
03
InvFrqNom
220# Set Battery
Menu
Parame
nr.
ter.Nr.
221# Bat Property
221
01
BatTyp
221
02
BatCpyNom
221
03
BatVtgNom
221
04
BatTmpMax
221
05
BatTmpStr
221
06
ChrgCtlOp
222# Bat Chargemode
222
01
BatChrgCurMax
Technical Description
Parameter Name
V
A
Hz
Parameter Name
VRLA
FLA
NiCd
Ah
V
degC
degC
A
Range/Unit
Default
value
230
9.6
50
Range/Unit
Default
value
VRLA
140
24
40
35
Auto
80
Parameter List Overview
Description
Nominal inverter voltage
Maximum AC charging current
Nominal inverter frequency
Description
Battery type:
= valve regulated lead acid
= flooded lead acid
= nickel cadmium
can only be changed in QCG
Nominal battery capacity (E:C10/U:C20)
can only be changed in QCG
Nominal battery voltage
can only be changed in QCG
Maximum battery temperature
battery restart temperature following stop
due to overtemperature
Type of DC charging device
Battery charging current limit (depends on
nominal battery capacity), 60 % of the
nominal battery capacity (221.02)
SI2012_2224-TEN082311
167

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny island 2224

Table of Contents