Refer to the following table for the preferred values for the finishing charge rates and charge
voltages for the battery types which may be used in the system, unless the battery manufacturer has
determined other values:
Maximal charging voltage in
[V/cell]
Type
1.4
1.55
1.6
1.65
2.25
2.4
2.5
2.6
*These values are valid only for battery types with low antimony content (SB < 3 %)
Consult the appropriate battery manufacturer for other battery type values.
Technical Description
maximal finishing charge rate I
FLA*
-
-
-
-
0.5
2
4
6
in [A/100 Ah]
Gas
VRLA
-
-
-
-
0.1
0.8
1.5
6
SI2012_2224-TEN082311
Installation
NiCd
0.5
5
5
5
-
-
-
-
35