SMA Sunny Island 2012 Technical Description page 171

Stand-alone grid inverter
Table of Contents

Advertisement

SMA Solar Technology AG
Menu
Parame
nr.
ter.Nr.
233
07
GnStrMod
233
08
GnOpTmMin
233
09
GnStpTmMin
233
10
GnCoolTm
233
11
GnErrStpTm
233
12
GnWarmTm
233
13
GnRvPwr
233
14
GnRvTm
233
15
GnCtlMod
233
20
GnAISns
234# Gen Start
234
01
GnAutoEna
234
02
GnAutoStr
234
03
GnSocTm1Str
234
04
GnSocTm1Stp
234
05
GnSocTm2Str
234
06
GnSocTm2Stp
234
07
GnTm1Str
234
08
GnTm2Str
234
09
GnPwrEna
Technical Description
Parameter Name
Manual
Automatic
start
GenMan
min
min
min
h
sec
W
sec
Cur
CurFrq
Low,
Medium
standard
High
Off
On
%
%
%
%
hhmmss
hhmmss
Off
On
Range/Unit
Default
value
Automatic
start
15
15
5
6
60
100
30
Cur
standard
On
3
40
80
40
80
0
0
Off
Parameter List Overview
Description
Generator interface
Minimum generator operating time
Minimum generator stop time
Cooling time for Generator
Generator stop time in case of generator
failure
warm up time (minimum time required
for generator voltage and frequency to
be within permissible range for
connection)
allowable generator reverse power
(active power)
allowable time for reverse power/
reverse current
External (Gen/Grid) control
(Current or frequency)
AI sensitivity
activate generator autostart
Number of automatic starts
SOC limit for switching on generator for
time 1
SOC limit for switching off generator for
time 1
SOC limit for switching on generator for
time 2
SOC limit for switching off generator for
time 2
time 1 for generator request
(begin time 1, end time 2) (hhmmss)
time 2 for generator request
(begin time 2, end time 1) (hhmmss)
activate generator request as a result of
power
SI2012_2224-TEN082311
171