Troubleshooting/Problem Solving
Display
Level
number
Category SYS
W702
1
internal restart
F703
3
Time limit exceeded during internal processing
F704
4
DSP invalid calibration
F705
4
Watchdog DSP triggered
F706
4
watchdog meter has expired (watchdog triggered several times in succession)
F707
4
watchdog meter on slave 1 has expired (watchdog triggered several times in succession)
F708
4
watchdog meter on slave 2 has expired (watchdog triggered several times in succession)
F709
4
watchdog meter on slave 3 has expired (watchdog triggered several times in succession)
F710
4
autostart counter expired (several autostarts in succession)
F711
2
DSP hardware error
F712
2
internal monitoring electronics (HTSS error)
W713
1
watchdog triggered
F714
2
internal overvoltage
F722
3
Short circuit in battery temperature sensor
F723
3
Defective cable in battery temperature sensor
W738
1
Synchronization was not conducted
F739
3
internal device communication BFR-DSP missing
F740
3
internal device communication BFR-DSP missing on slave 1
F741
3
internal device communication BFR-DSP missing on slave 2
F743
3
internal device communication BFR-DSP missing
W753
1
Invalid date (date is set automatically when launched)
W755
1
Battery preservation mode level 1
W756
1
Battery preservation mode level 2
W757
1
Battery preservation mode level 3
F762
4
Short circuit or ruptured cable on transformer temperature
F766
4
Short circuit or ruptured cable on transformer temperature sensor/inverter
W770
1
Short circuit at the 24 V DC-output
W851
1
Battery connection polarity reversed or short-circuit at first SIC40
W852
1
Battery excess voltage (>65 V) at first SIC40
W853
1
PV generator excess voltage at first SIC40
W854
1
PV voltage absent or short-circuit at first SIC40
W855
1
Sensor fault or temperature deficit at first SIC40