Parameter List Overview
Menu
Parame
nr.
ter.Nr.
222
02
AptTmBoost
222
03
AptTmFul
222
04
AptTmEqu
222
05
CycTmFul
222
06
CycTmEqu
222
07
ChrgVtgBoost
222
08
ChrgVtgFul
222
09
ChrgVtgEqu
222
10
ChrgVtgFlo
222
11
BatTmpCps
168
SI2012_2224-TEN082311
Parameter Name
min
h
h
d
d
V
V
V
V
mV/degC
Range/Unit
Default
value
120
5
10
14
180
2.4
2.4
2.4
2.25
4.0
SMA Solar Technology AG
Description
Absorption time at normal charge
120 = VRLA
90 = FLA
300 = NiCd
depending on the setting in QCG
Absorption time at full charge
5 = VRLA
5 = FLA
7 = NiCd
depending on the setting in QCG
Absorption time at equalizing charge
10 = VRLA
10 = FLA
10 = NiCd
depending on the setting in QCG
Full charge cycle time
Cycle time at equalizing charge
Setpoint of cell voltage at normal charge
2.4 = VRLA
2.55 = FLA
1.65 = NiCd
depending on the setting in QCG
Setpoint of cell voltage at full charge
2.4 = VRLA
2.5 = FLA
1.65 = NiCd
depending on the setting in QCG
Setpoint of cell voltage at equalizing
charge
2.4 = VRLA
2.5 = FLA
1.65 = NiCd
depending on the setting in QCG
Setpoint of cell voltage at floating charge
2.25 = VRLA
2.25 = FLA
1.55 = NiCd
depending on the setting in QCG
Battery temperature compensation
4.0 = VRLA
4.0 = FLA
0.0 = NiCd
depending on the setting in QCG