X1 Supply; Indicators - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

7.3.7

7.4 Indicators

LED
Color
Function
H1
Red
Power Down Ready
H401
Yellow
Supply output 1 (F401)
H402
Yellow
Supply output 2 (F402)
H501
Yellow
Monitored alarm output (F501)
H601
Yellow
Monitored fault output (F601)
Building Technologies
Fire Safety

X1 supply

Pin
Designation
1
#BATT
2
#CONV
3
#MAINS
4
COMMON
5
3SRC+
6
3SRC–
7
VSYS+
8
VSYS+
9
VSYS–
10
VSYS–
Admissible cable cross-section: 0.2...2.5 mm²
X1
#BATT
#CONV
#MAINS
COMMON
3SRC+
3SRC-
VSYS+
VSYS+
VSYS-
VSYS-
Indications of supply and system
Periphery board (2 loops) FCI2002-A1
Description
Message input from the power supply: Battery fault
Message input from the power supply: Converter fault
Message input from the power supply: Mains failure
Ground
Supply input for third supply source (+) [FR]
Supply input for third supply source (–) [FR]
Supply input from the power supply (+)
Supply input from the power supply (+)
Supply input from the power supply (–)
Supply input from the power supply (–)
1
2
3
4
5
6
7
8
9
10
Condition Meaning
Off
Normal operation
On
Control panel may be disconnected from the
mains.
Off
Fuse ok
On
Fuse damaged
Off
Fuse ok
On
Fuse damaged
Off
Fuse ok
On
Fuse damaged
Off
Fuse ok
On
Fuse damaged