Fire detection system
Table of Contents

Advertisement

Element
Plugs and terminals
Slots for modules
LEDs
Fuses
Adjustment elements
Building Technologies
Fire Safety
Des.
Function
X1
Supply connection
X3
Connection periphery bus to the PMI & mainboard
X5
Monitored horn outputs
X6
Monitored outputs for Alarm and Fault
X7
Changeover contacts for RT Alarm and RT Fault
X8
Configurable inputs/outputs 1 ... 12 and supply outputs Vsys
X11
FDnet detector line, loop 1 (module 2)
X12
FDnet detector line, loop 2 (module 2)
X21
FDnet detector line, loop 1 (module 3)
X22
FDnet detector line, loop 2 (module 3)
X400
Connection periphery bus for additional peripherals
X401
Connection periphery bus for additional peripherals
X14
Connection to the LED emergency alarm indicator FTO2003 for the integrated
line card 1
X15
Loop extension (FDnet) FCI2003 for the integrated line card 1
X24
Connection to the LED emergency alarm indicator FTO2003 for the integrated
line card 2
X25
Loop extension (FDnet) FCI2003 for the integrated line card 2
X40
Not used
H1
Power Down Ready
H250
Display FDnet module 2
H850
Display FDnet module 3
H401
Monitoring supply output 1 (fuse F401)
H402
Monitoring supply output 2 (fuse F402)
H501
Monitoring alarm output (fuse F501)
H601
Monitoring fault output alarm output (fuse F601)
H100-
Indications of the programmable I/Os
H120
F400
Horn output 1 (1 A/T); Schurter OMT 125
F401
Supply output 1 (1 A/T); Schurter OMT 125
F402
Supply output 2 (1 A/T); Schurter OMT 125
F403
Horn output 2 (1 A/T); Schurter OMT 125
F501
Monitored alarm output (1 A/T); Schurter OMT 125
F601
Monitored fault output (1 A/T); Schurter OMT 125
S100
Switchover of the LED indicators for the I/Os
Periphery board (4 loops) FCI2004-A1