34
CPU card (FC2080) FCC2004-A1
Adjustment elements
34.5
34.6
Supply input
Display
Interfaces
Mechanical data
200
Building Technologies
Fire Safety
Adjustment elements
The only setting element for the user is the S8 button next to the LED matrix
display. The LED matrix display changes through the following list with a brief push
of a button for <0.5 seconds.
Display Function
R
Reset
L
Access Level 3
1
F
Factory reset
1
U
Firmware
Update
S
Switch over'
D
Debug mode
These functions are displayed only on the active CPU.
1
The displayed function is executed at the push of a button for >1.5 seconds.
If the button is not actuated for 5 seconds, then the LED matrix display in the
standard display is switched on.
Technical data
Voltage
Quiescent current at 24 V with
SAFEDLINK module
Maximum current at 24 V with
SAFEDLINK module
Dual operation possible with CPU card
(FC2080)
LED matrix display 5 x 7 LED
LED diameter
1 x plug for serial modules
2 x Ethernet connection RJ45
Dimensions (W x H x D)
Weight (without FN2010-A1)
Weight (with FN2010-A1)
Description
Initiate restart/booting
System works at access level 3 after PIN has been entered
Restore to factory setting and restart/boot
Firmware of the main CPU is updated
Transfer of control to the second CPU card
Test mode for developers
DC 20...30 V
140 mA
180 mA
FCC2004-A1
17.8 x 12.7 mm
2 mm
Card cage (CPU)
10/100 Mbit/s
35.2 x 189 x 139.1 mm
206 g
226 g
008837_q_en_--
14.05.2012