Siemens 13-xx-ST-SBT Series Product Data page 179

Fire detection system
Table of Contents

Advertisement

Monitored output
RT alarm/horn
Configurable inputs/outputs
1 ... 2
Mechanical data
Ambient conditions
Standards and approvals
Building Technologies
Fire Safety
Designation
Design
Output voltage
Output current
Loading capacity
Monitored for (active and inactive)
Measuring range, monitoring resistor
Range of termination resistor
(Reol) for load with diode
decoupled (EN54)
Range of the load resistance
(Rload) with load resistor
monitoring (VdS)
Line resistance (both cables)
Monitoring tolerance
Measurement cycle
Status monitoring
Duration of the monitoring interruption
when activation was deactivated.
Duration of calibration
Designation
Individually configurable as
Configured as input:
Design
Threshold values
Configured as output:
Design
Output voltage
Output current per output
Dimensions (L x W x H)
Weight
Operating temperature
Storage temperature
Air humidity
VdS
QA Standards
CE conformity mark
LPCP
I/O card (RT) FCI2007-A1
'Fire Output 1+'; 'Fire Output 1-'
'Fire Output 2+'; 'Fire Output 2-'
Load or
EOL monitoring with calibration
Monitored fuse in operation
Activated in degraded mode operation (RT
alarm/horn can be switched off)
DC 26.4...27.6 V (DC 27.2 V -3 % +1.5 %)
Max. 2 A
Max. 470 µF
Short-circuit
Open line
40...6100
45...5500
45...5200
Max. 200
Load resistance monitoring (VdS): ± 10 %
Load with diode decoupled (EN 54): ±7.1 %
transient ±2.5 %
1 s
4 s
30 s
25 s
'RT_Response/GPIO1' and 'GPIO2'
Input
Output
Digital
Not monitored
GPIO1 configurable as RT_Response possible
>18 V = off
<9 V = on
Open drain
Inherently short-circuit-proof
DC 26.4...27.6 V (DC 27.2 V -3 % +1.5 %)
Max. 300 mA
160 x 120 x 15 mm
119 g
Min. -5 °C max. +50 °C
Min. -20
max. +60
Max. 93 % rel. air humidity (EN 60068-2)
30
Technical data
179
008837_q_en_--
14.05.2012

Advertisement