Pin Assignments; Connector X3; Plug X2 - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

18.3
18.3.1
18.3.2
Building Technologies
Fire Safety

Pin assignments

Connector X3

Pin
Designation
1
A1
2
B1
3
S
4
D
5
E
6
S
7
A2
8
B2
FN2002
FCnet
FCM200x
X13
A1
B1
A2
B2
4
3
2
1
X3
FN2001
+Usys
-Usys
FC20xx
Repeater FN2002, cabling
In the FCnet, line 1 must always be wired to line 2 or line 2 must be wired to line 1,
respectively.

Plug X2

Pin
Designation
1
+Usys
2
-Usys
3
+Usys
4
-Usys
"Input" and "Output" are connected in parallel on the printed circuit board and can
be switched.
Repeater (SAFEDLINK) FN2002-A1
Description
Line 1 (+)
Line 1 (-)
Shielding
Shielding
Ground connection
Shielding
Line 2 (+)
Line 2 (-)
X3
X2
1
8
1
A1
B1
S
D
E
S
A2
B2
+
-
Description
Supply input DC +24 V
Supply input 0 V
Supply output DC +24 V
Supply output 0 V
Pin assignments
4
-
+
FCnet
FCM200x
X13
A1
B1
A2
4
3
X3
FN2001
FC20xx
008837_q_en_--
18
B2
2
1
113