39
Floor repeater terminal FT2010

Technical data

39.5
Supply
External supply
Detector line
Functional data
Connections
Ambient conditions
Mechanical data
Standards
226
Building Technologies
Fire Safety
Technical data
Optional
Designation
Voltage
Power consumption
Designation
Voltage
Power consumption
Without external supply
With external supply
Maximum current connection factor
Without external supply
With external supply
Quiescent current connection factor
Without external supply
With external supply
Address connection factor
Separator connector factor
Protocol
Display
Acoustic signaling
Detector line and external supply
Design
Cable cross-section
Operating temperature
Storage temperature
Protection category
Max. application height
Dimensions (W x H)
Depth of FT2010-A1
Depth of FT2010-C1
Weight of FT2010-A1
Weight of FT2010-C1
Safety
QA Standards
CE conformity mark
Via external supply
Via FDnet detector line
'AC+', 'AC–'
AC 15...18 V
DC 20...30 V
10 ... 50 mA
'LINE+', 'LINE–'
DC 12...32 V
4...40 mA
Max. 5 mA
160
20
20
20
1
1
FDnet
6 lines of 40 characters each
Tone interval can be configured with
SintesoWorks
Screw terminals
0.8 ... 1.5 mm
2
-8...+42 °C
-20...+60 °C
IP30
4000 m above sea level
283 x 207 mm
79 mm
45 mm
800 g
1100 g
EN 60950
Siemens Standard SN 36350
ISO 9001
ISO 14001
Yes