X11 Monitoring Signals - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

5.3.3
Building Technologies
Fire Safety

X11 monitoring signals

Pin
Designation
9
SB
8
SB
7
SA
6
SA
5
F
4
F
3
BS
2
NS
1
S
Admissible cable cross-section: 0.2...2.5 mm²
SV 24V-150W-A5
X11
SB
9
SB
8
SA
7
SA
6
F
5
F
4
BS
NO
3
NO
NS
2
C
S
1
X8
+B
0
I-begr.
T6.3A
I-unbegr.
9
+B
8
+24V
+24V
7
+24V
6
5
+24V
+24V
4
+24V
0V
3
2
0V
1
0V
Wiring of the single power supply SV 24V-150W-A5
1
Cable tree to periphery board or fire terminal board
Power supply (150 W) SV 24V-150W-A5
Description
Control line B for even current distribution (only when
switching in parallel)
Control line B for even current distribution (only when
switching in parallel)
Control line A for even current distribution (only when
switching in parallel)
Control line A for even current distribution (only when
switching in parallel)
Connection for temperature sensor (master only)
Connection for temperature sensor (master only)
Signaling: Battery fault (normal operation 1/3 closed)
Signaling: Mains fault (normal operation 1/2 closed)
Signaling: Common fault contact
NTC 4.7 k
5
Pin assignments
#BATT
#MAINS
COMMON
1
VSYS+
VSYS-
Battery
37