Siemens 13-xx-ST-SBT Series Product Data page 133

Fire detection system
Table of Contents

Advertisement

Building Technologies
Fire Safety
Reset button
The Reset button is above the C-plug and has two functions:
Restart
The module is restarted. The loaded configuration is retained.
Press the Reset button for less than 5 seconds.
The module is restarted.
The fault LED lights up yellow. A restart takes around 2 minutes.
After the restart, the fault LED lights up green.
Reset the configuration to the factory settings
The module is restarted and reset to its original state. The loaded configuration
is deleted.
Press the Reset button until the fault LED flashes yellow/red (press for
more than 5 seconds).
After resetting, the module restarts automatically. The fault LED lights up
yellow.
After the restart, the fault LED lights up green.
C-plug (option)
The C-plug is an optional removable medium for storing the FN2009-A1's
configuration data. When replacing the device, the configuration data can be easily
transferred by removing the C-plug. The C-plug must be ordered separately. You
will find details on this in document 008843.
Safety module (firewall) FN2009-A1
Adjustment elements
21
133
008837_q_en_--
14.05.2012