43.5
Fire department control panel
(FBF)
Remote transmission /
transmission device
Releasing element (FSE)
Building Technologies
Fire Safety
Technical data
Supply voltage
Supply current
Design of the inputs and outputs
Line resistance per wire
Supply voltage
Supply current
Output (RT/RD alarm):
Voltage/current (if active)
Design
In quiescent condition monitored for
Load resistance
Line resistance per wire
Input (RT/RD confirmation):
Design
Line resistance per wire
Input FSE:
Design
Termination resistor for quiescent condition
Termination resistor for alarm
Monitored for
Line resistance per wire
Fire brigade periphery module FCI2001-D1 [DE]
24 V
Type <50 mA, max. 1A (current limited)
Active low
Short-circuit-proof
Max. 10
24 V
Typ. <30 mA, max. 1A (current limited)
24 V; 12 ... 120 mA; max. 1 A
Active high
Short-circuit-proof
Current limited
Short-circuit (incl. gradual)
Open line (incl. gradual)
200
... 2 k
Max. 10
Active low
Short-circuit-proof
Max. 10
Short-circuit-proof
3.3 k
3.3 k parallel 680
Short-circuit
Open line
Max. 10
43
Technical data
247