Technical Data - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

28
I/O card (programmable) FCI2008-A1

Technical data

28.6
General
Supply
Supply outputs 1 and 2
Configurable
Inputs/outputs 1...12
Mechanical data
Ambient conditions
Standards and approvals
164
Building Technologies
Fire Safety
Technical data
Number of freely programmable I/Os
Ground fault detection
Operating voltage
Operating current
Designation
Voltage
Current
Designation
Individually configurable as
Configured as input:
Design
Threshold values
Configured as output:
Design
Output voltage
Output current per output
Output current of all outputs (total)
Configuration of degraded mode behavior
Dimensions (L x W x H)
Weight
Operating temperature
Storage temperature
Air humidity
VDS
QA Standards
CE conformity mark
LPCP
12
Via PMI & mainboard
Vsys 20...30 V
Max. 2 A
'VSYS_01', 'VSYS_02'; 'GND'
DC 21...28.6 V
Max. 1 A (protected with 1 AT)
'I/O1' ... 'I/O12'
Input
Output
Digital
Not monitored
> Vsys/2 = off
< Vsys/4 = on
Open drain
Inherently short-circuit-proof
Excess temperature protection
DC 21...28.6 V
max. 300 mA
1.5 A
Open
Closed
Fixed
Alternating quickly
Alternating slowly
Activated by horn emergency alarm
160 x 120 x 15 mm
104 g
Min. -5 °C max. +50 °C
Min. -20
max. +60
Max. 93 % rel. air humidity (EN 60068-2)
008837_q_en_--
14.05.2012

Advertisement

Table of Contents
loading

Table of Contents